Press ESC to close

VPD in practice: how to dial temperature and humidity in veg and flower

VPD (Vapour Pressure Deficit) is the simplest metric that ties together temperature, humidity and how the plant drinks/transpires. Good VPD = steady growth, turgid leaves, fast nutrient uptake and less mold. Below you’ve got ready ranges, an RH→kPa table, a leaf-temperature correction (LED vs HPS) and real tent settings.


Table of contents

  1. TL;DR / Quick start
  2. Target VPD ranges (veg/flower)
  3. “Set RH, hit VPD” table
  4. LED/HPS correction (leaf temperature)
  5. Real-life settings (small/medium tent)
  6. How to calculate VPD in 10 seconds
  7. Most common mistakes + quick fixes
  8. FAQ
  9. Checklists

TL;DR / Quick start

  • Vegetative: aim for 0.8–1.2 kPa (vigorous growth, leaves packed with water).
  • Flowering:1.2–1.6 kPa, and 1.4–1.8 kPa in late flower (drier flowers, lower mold risk).
  • Set temperature first, then RH until you hit the VPD target.
  • Under LED the leaf is often ~1 °C cooler than air → actual VPD is ~0.17–0.22 kPa lower than the chart. Under HPS often +1 °C~0.18–0.23 kPa higher.

Target VPD ranges (veg/flower)

  • Clones/seedlings:0.6–0.9 kPa (high humidity, gentle conditions).
  • Veg:0.8–1.2 kPa (balanced growth and uptake).
  • Early flower (stretch):1.1–1.4 kPa.
  • Mid/late flower:1.4–1.8 kPa (firmer conditions, drier buds).

Stability matters more than chasing the absolute top values.


“Set RH, hit VPD” table

Assume leaf temp ≈ air temp (see the next section for correction). Find your air temperature, pick a VPD target and set RH:

Air temp.RH for 0.9 kPa (veg)RH for 1.2 kPa (veg/flower)RH for 1.5 kPa (flower)
20 °C61.5%48.7%35.8%
22 °C66.0%54.6%43.3%
24 °C69.8%59.8%49.7%
26 °C73.2%64.3%55.4%
28 °C76.2%68.3%60.3%

How to use it? Example: you’ve got 24 °C and target 1.5 kPa in bloom → set ~50% RH. If you miss, adjust humidity first, then temperature by 1–2 °C.


LED/HPS correction (leaf temperature)

VPD should be based on leaf temperature, not just room air.

  • LED: leaf often ~1 °C cooler → from the table value subtract ~0.17–0.22 kPa (warmer rooms need the larger correction).
  • HPS: leaf often ~1 °C warmeradd ~0.18–0.23 kPa.

Tip: a cheap IR thermometer shows leaf–air delta in a second.


Real-life settings (small/medium tent)

Setup A — 60×60×160 cm, LED 150 W

  • Veg (target ~1.1 kPa): 24 °C, 60% RH → chart ~1.2 kPa; LED (leaf ~23 °C) ≈ ~1.05 kPa.
    Gear: ultrasonic humidifier + outlet controller (humidistat).
  • Mid flower (target ~1.5 kPa): 26 °C, 55% RH → ~1.5 kPa; LED correction ≈ ~1.33 kPa (fine — dense plants will “push” VPD up anyway).
  • Late flower (target ~1.6–1.7 kPa): 24–25 °C, 45–50% RH.
    Gear: small dehumidifier (200–500 ml/day) + exhaust control.

Setup B — 80×80×180 cm, HPS 250 W

  • Veg: 24 °C, 55–60% RH → ~1.2 kPa; HPS (leaf ~25 °C) ≈ ~1.38 kPa — trim RH to 58–60% or drop temp to 23 °C to get back near 1.1–1.2 kPa.
  • Flower: 25–26 °C, 45–50% RH → ~1.5–1.6 kPa; HPS correction adds ~0.18–0.20 kPa, so stick near 50% RH.
  • Night: allow 2–3 °C drop, but ensure RH doesn’t spike >60% late in flower (if it does — dehumidifier overnight).

Rough budget (PLN):
humidifier 150–300, dehumidifier 500–1200, controller/humidistat 120–200, IR thermometer 60–120, T/RH sensor 20–50.


How to calculate VPD in 10 seconds

For quick math use VPD ≈ SVP(air) × (1 − RH/100), where SVP(air) is saturation vapor pressure at air temperature.

  • Rule of thumb: raise temp → SVP rises → VPD rises (at constant RH).
  • Second rule: raise RH → VPD drops (at constant temp).
    For precision you’d use SVP(leaf), but in practice the table + LED/HPS correction is enough.

Most common mistakes + quick fixes

  1. Too low VPD (too humid): puffy leaves, slowed uptake, mold risk.
    Fix: raise temp by 1–2 °C or drop RH by 5–10 pp (dehumidifier / stronger exhaust).
  2. Too high VPD (too dry): leaf edges curl, plant burns through water.
    Fix: raise RH by 5–10 pp (humidifier) or lower temp by 1–2 °C.
  3. Night RH spike: lights off → temp drops → RH shoots up.
    Fix: less humidifying late day, overnight dehumidifier, constant exhaust.
  4. Ignoring leaf temperature: under LED you think you’re at 1.4 kPa but it’s ~1.2.
    Fix: check with IR thermometer and correct as above.

FAQ

Do I need one “perfect” VPD the whole run?
No. Ramp it: lower for clones/veg, higher in bloom. Stability > perfection.

I only have a hygrometer and thermometer. Enough?
Yes — use the table and tweak slowly. An IR thermometer is a cheap upgrade.

Does CO₂ change my VPD target?
With elevated CO₂ (e.g., 800–1200 ppm) plants tolerate slightly higher VPD (especially in flower). Without enrichment, stick to standard ranges.

Is 40% RH too low in late flower?
Not if temperature is moderate. That’s high VPD — plants will drink faster; monitor irrigation and EC to avoid overdrying.


Checklists

Checklist — Hit your VPD target

  • Set target VPD for the phase (e.g., 1.5 kPa in flower).
  • Set day temperature (e.g., 26 °C).
  • From the table set RH (e.g., 55%).
  • Check leaf temp (IR), correct by ±0.2 kPa (LED/HPS).
  • Log and keep daily stability.

Checklist — Gear & control

  • Humidifier/dehumidifier on a humidistat.
  • Exhaust and fans positioned to avoid direct leaf cooling.
  • Night: manage RH spike (dehumidifier/exhaust).
  • Log T/RH once daily; change in small steps.
Manolo MJF

Hey, I’m Manolo from MJF – your go-to grow buddy 🌿. I blog about everything cannabis cultivation: from sprouting your first seed to harvesting top-shelf buds. Whether you're growing in a closet or a custom-built growroom, I’m here to share tips, tricks, and tried-and-true methods to keep your plants (and you) thriving. Light it up with knowledge and let’s grow together! 💡🌱 #GrowWithManolo

Leave a comment

Your email address will not be published. Email is optional. Required fields are marked *

Your experience on this site will be improved by allowing cookies. Read more